Circuit
Breaker
Model
VT130H7U
Rating
(Amps)
4015
15
4025
15
4035
15
4055
15
4080
30
4110
30
4160
40
4220
50
4270
70
4330
90
4400
100
4500
100
4600
125
4750A
175
410KA
200
412KA
225
415KA
300
420KA
350
425KA
400
430KA
600
435KA
700
Note:
(*) Indicates that the item is one of a set of two parallel cables.
206
Table 15. 460 Volt Drive Cable/Terminal Specifications.
Typical Cable Size (AWG)
Input/Output
AM, FM, and II
Power Wire
Terminals
Size
#14
#14
#14
#14
#14
#14
#10
#10
#8
#8
#20
#6
(3-core shield)
#4
#3
#2
#1
#2/0
*#4/0
*#2/0
*#4/0
*#300
*#400
Appendix E
Control Terminal
ASD Input/Output Power
Strip
Lug Wire Capacity
8 to 24 AWG
4 to 18
#18
(2-core shield)
14 to 1/0
6 to 250