F402
Motor Constant 1 (primary resistance)
Program
Motor Parameters
⇒
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
saving, the Motor Constant setting (motor tuning) is required.
Motor Constant 2 (secondary resistance)
Program
⇒
Motor Parameters
This parameter is the measurement of the rotor resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
This setting is used to maximize the effectiveness of the Vector Control,
Automatic Torque Boost, or Automatic Energy-saving functions.
Motor Constant 3 (exciting inductance)
Program
⇒
Motor Parameters
This parameter is used to input the excitation inductance for the motor. This
value is used in conjunction with other constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Motor Constant 4 (load inertia)
Program
Motor Parameters
⇒
This parameter is used to control the load inertia during speed changes.
Acceleration and deceleration overshoot may be reduced by increasing this
value.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Motor Constant 5 (leakage inductance)
Program
⇒
Motor Parameters
This parameter provides slight increases in the output voltage of the drive at the
high speed range.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
H7 ASD Operation Manual
Vector Motor Model
⇒
⇒
Vector Motor Model
⇒
Vector Motor Model
Vector Motor Model
⇒
⇒
Vector Motor Model
Direct Access Number — F402
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100,000 MΩ
Units — Ω
Direct Access Number — F403
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — Open
Units — Ω
Direct Access Number — F404
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 6500.0
Units — µH
Direct Access Number — F405
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Direct Access Number — F410
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 650.0
F410
123