F206
VI/II Torque Reference Setpoint #2 (%)
Program
Torque Setting Parameters
⇒
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level and motor load.
See
F201
for further information on this setting.
This parameter sets Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with the setting of F203. This value is entered as
0 to 250% of the rated torque.
Frequency Mode #2
Program
⇒
Fundamental Parameters
This parameter selects the source of the frequency command signal to be used
as Frequency Mode #2 in the event that Frequency Mode #1 is disabled or if
Frequency Mode #2 is set up as the primary control parameter. See
additional information on this setting.
Settings:
Use VI/II
Use RR
Use RX
Use Option Card RX2
Use LED Keypad Option
Use Binary/BCD Input
Use EOI
Use RS232/485
Use Communication Card
Use Motorized Pot. Simulation
Use Pulse Input Option
Mode #1/#2 Switching Frequency
Program
⇒
Fundamental Parameters
Mode #1/#2 Switching Frequency
This parameter sets the threshold frequency that will be used in
determine if Frequency Source #1 or #2 will control the output of the ASD.
See
F200
for additional information on this setting.
86
Setpoints
VI/II
⇒
⇒
⇒
Standard Mode Selection
F200
⇒
Standard Mode Selection
F200
to
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
Direct Access Number — F207
Parameter Type — Selection List
Factory Default — VI/II
Changeable During Run — Yes
for
Direct Access Number — F208
⇒
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — Max. Freq. (F011)
Units — Hz
H7 ASD Operation Manual
F208