F616
Overtorque Trip/Alarm Level (Positive Torque)
Program
Protection Parameters
This parameter sets the torque threshold level that is used as a setpoint for
overtorque tripping. This setting is a percentage of the maximum rated torque
of the drive.
Overtorque Trip/Alarm Level (Negative Torque)
Program
Protection Parameters
This parameter sets the torque threshold level that is used as a setpoint for
overtorque tripping during regeneration. This setting is a percentage of the
maximum rated torque of the drive.
Overtorque Detection Time
Program
Protection Parameters
This parameter sets the amount of time that the overtorque condition may
exceed the tripping threshold level set at
Cooling Fan Control
Program
Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
Automatic
Always On
Cumulative Run Timer Alarm Setting
Program
Protection Parameters
This parameter sets a run-time value that, once exceeded, closes a contact. The
output signal may be used to control external equipment or used to engage a
brake.
Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
158
Overtorque Parameters
Overtorque Parameters
Overtorque Parameters
F616
and
F617
before a trip occurs.
Cooling Fan Settings
Cumulative Run Timer
Direct Access Number — F616
Parameter Type — Numerical
Factory Default — 150.0
Changeable During Run — No
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F617
Parameter Type — Numerical
Factory Default — 150.0
Changeable During Run — No
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F618
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — No
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Direct Access Number — F620
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
Direct Access Number — F621
Parameter Type — Numerical
Factory Default — 175.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 100)
H7 ASD Operation Manual