F372
Position Completion Range
Program
Feedback Parameters
During a deceleration ramp, this parameter sets a speed range that must be
attained before the Stop command may be executed.
Frequency Limit at Position
Program
Feedback Parameters
While operating in the Position-Control mode and using PG feedback, this
setting determines the maximum acceleration rate in Hz/second.
Current Control Proportional Gain
Program
Feedback Parameters
This parameter sets the sensitivity of the drive when monitoring the output
current to control speed. The larger the value entered here, the more sensitive
the drive is to changes in the received feedback.
Current Control Integral Gain
Program
Feedback Parameters
This parameter sets the degree and rate at which the output frequency will be
allowed to change when prompted by changes in the output current.
The larger the value entered here, the quicker/more the drive responds to
changes in feedback.
Speed Loop Proportional Gain
Program
Feedback Parameters
This parameter sets the Proportional Gain (sensitivity) of the drive when
monitoring the PG signal to control speed. The larger the value entered here,
the more sensitive the drive is to changes in the received feedback and the
quicker it responds.
H7 ASD Operation Manual
PG Settings
PG Settings
PG Settings
PG Settings
PG Settings
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 4000
Direct Access Number — F373
Parameter Type — Numerical
Factory Default — 800
Changeable During Run — Yes
Minimum — 1
Maximum — 8001
Units — Hz/Second
Direct Access Number — F374
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 100.0
Maximum — 1000
Direct Access Number — F375
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 100.0
Maximum — 1250
Direct Access Number — F376
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 3.2
Maximum — 1000
F376