F300
PWM Carrier Frequency
Program
Special Control Parameters
This parameter sets the frequency of the pulse width modulation signal applied
to the output waveform.
Note: For proper operation, the carrier frequency must be 2.2 kHz or above
except when operating in the Constant Torque, Variable Torque, or the
5-Point Setting modes.
Break/Make ST
Program
Protection Parameters
This parameter Enables/Disables the ability of the drive to start into a spinning
motor when the ST – CC connection momentarily opens and is then closed
(Break/Make ST) or after a power interruption (momentary power failure). This
parameter also Enables/Disables
Ridethrough Mode
Program
Protection Parameters
This parameter determines the motor-control response of the drive in the event
of a momentary power outage.
Settings:
Off
Ridethrough
Stop
Number of Retries
Program
Protection Parameters
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted.
See the section titled
Safety Precautions on pg. 2
setting.
H7 ASD Operation Manual
Carrier Frequency
Retry/Restart
F312
and F313.
Undervoltage/Ridethrough
Retry/Restart
for further information on this
Direct Access Number — F300
Parameter Type — Numerical
Factory Default — 2.200
Changeable During Run — No
Minimum — 0.500
Maximum — 15.000
Units — kHz
Direct Access Number — F301
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F302
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — Yes
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
F303
109