Configure Single Pid Controller - ABB AX410 User Manual

Single and dual input analyzers for low level conductivity
Hide thumbs Also See for AX410:
Table of Contents

Advertisement

...5 PROGRAMMING
...5.8 Configure Control

...5.8.1 Configure Single PID Controller

Output Type
set to
Time
10. 0
Secs
Cycle Time
PID Controller
Output Type
set to
Analog
4-20mA
0-20mA
----
0-10mA
Output Range
PID Controller
44
Time Proportioning Output
The time proportioning output value is calculated using the following equation:
control output x cycle time
on time =
100
Set the cycle time, between 1.0 and 300.0 seconds in 0.1 second increments – see
Appendix B, Fig. B4 Mode C.
Note. Changes to the cycle time do not take effect until the start of a new cycle.
Output = 0%
Energized
Output = 25%
De-energized
Energized
Output = 50%
De-energized
Energized
Output = 75%
De-energized
Output = 100%
See Section 5.8.2.
Power Recovery
See Section 5.9.
CONFIG. SECURITY
Analog Output
Set the analog current output range.
See Section 5.8.2.
Power Recovery
See Section 5.9.
CONFIG. SECURITY
Permanently de-energized
2.5s
7.5s
5s
7.5s
Permanently energized
Cycle Time = 10s
5s
2.5s