...5.8 Configure Control

5.8.1 Configure Single PID Controller
Controller
set to
PID
----
PID Controller
Rev.
----
Direct
Control Action
100. 0
% Man
Prop. Band
100
Secs
Integral Time
10. 0
Secs
Derivative Time
Pulse
Analog
----
Time
Output Type
See Section 5.8.2.
Power Recovery
Control Action
Set the required control action:
Rev.
– Reverse acting – see Appendix B, Fig. B2.
Direct
– Direct acting – see Appendix B, Fig. B3.
Proportional Band
Set the required proportional band, between 0.0 and 999.9% in 0.1% increments.
Integral Action Time
Set the integral action time, between 1 and 7200 seconds in 1 second increments.
Set to
to disable integral action time.
OFF
Derivative Action Time
Set the derivative action time, between 0.1 and 999.9 seconds in 0.1 second increments.
Set to
to disable derivative action time.
OFF
Output Type
Set the required output type:
– Time proportioning (relay 1)
Time
Analog
– Analog output (analog output 1)
Pulse
– Pulse frequency (relay 1)
set to
Output Type
Cycle Time
set to
Output Type
Output Range
set to
Output Type
Pulses/Minute
– continued on next page.
Time
– continued on next page.
Analog
– continued on page 45.
Pulse
5 PROGRAMMING...
43