ABB AX411 User Manual
ABB AX411 User Manual

ABB AX411 User Manual

Ax400 series dual input conductivity analyzer
Hide thumbs Also See for AX411:

Advertisement

Quick Links

AX400 Series
User Guide
Model AX411
Dual Input Conductivity Analyzer

Advertisement

Table of Contents
loading

Summary of Contents for ABB AX411

  • Page 1 AX400 Series User Guide Model AX411 Dual Input Conductivity Analyzer...
  • Page 2 We are an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liquid analysis and environmental applications. Cert. No. Q05907 As a part of ABB, a world leader in process automation technology, we offer customers application expertise, service and support worldwide. EN 29001 (ISO 9001) We are committed to teamwork, high quality manufacturing, advanced technology and unrivalled service and support.
  • Page 3 CONTENTS Section Page Section Page INTRODUCTION ............2 INSTALLATION ............29 Siting Requirements ......... 29 Mounting ............30 OPERATION ..............3 6.2.1 Wall-/Pipe-mount Analyzers ....30 Powering Up the Analyzer ........3 6.2.2 Panel-mount Analyzers ....... 31 Displays and Controls ........3 Connections, General ........
  • Page 4: Introduction

    1 INTRODUCTION This conductivity analyzer has been designed for continuous monitoring and control of conductivity. It is available in wall-/ pipe-mount or panel-mount versions and can be used with either one or two sensors, each with a temperature input channel. When used with two sensors, readings can be compared to produce a range of extrapolated values.
  • Page 5: Operation

    2 OPERATION 2.1 Powering Up the Analyzer 2.2.1 Key Functions Caution. Ensure connections made Menu 1 correctly, especially to the earth stud – see Section 6.3. Advance to next menu 1) Ensure the input sensors are connected correctly. Menu 2 2) Switch on the power supply to the analyzer.
  • Page 6 …2 OPERATION Use the Sidescroll Key to scroll through the Pages within each Menu Section 2.3, Page 6 Section 3.1, Page 7 Section 3.2, Page 8 Section 3.3, Page 8 Section 3.4, Page 9 Section 3.5, Page 9 OPERATING PAGE VIEW SETPOINTS VIEW OUTPUTS VIEW HARDWARE...
  • Page 7 2 OPERATION… Use the Sidescroll Key to scroll through the Pages within each Menu Section 5.4, Page 19 CONFIG.ALARMS Config. Alarm 1 Config. Alarm 2 Config. Alarm 3 Config. Alarm 4 Config. Alarm 5 A1: Type A2: Type A3: Type A4: Type A5: Type Use the Menu...
  • Page 8: Operating

    …2 OPERATION 2.3 Operating Page 2.3.1 Single Input Conductivity Measured Values 5. 0 00 uS/cm Conductivity. 25. 0 Deg.C Temperature. Conductivity See Section 3.1. VIEW OUTPUTS SENSOR CAL. If sensor calibration enabled – see Section 4.1. Security Code is not set to zero – see Section 5.1. Alter Sec.
  • Page 9: Operator Views

    3 OPERATOR VIEWS 3.1 View Set Points View Set Points This page shows alarm set points. The value of each of the set points is shown, together with the name of the parameter it's assigned to. ----- Set point values and relay/LED actions are programmable – see Section 5.4. VIEW SETPOINTS Sensor A (Conductivity), Alarm 1 Set Point Sen.A...
  • Page 10: View Outputs

    …3 OPERATOR VIEWS 3.2 View Outputs Theoretical Analog Output There are up to four analog outputs, each showing information for one sensor: ----- Note. Analog outputs 3 and 4 are available only if the optional analog output board is fitted. VIEW OUTPUTS 12.
  • Page 11: View Software

    3 OPERATOR VIEWS 3.4 View Software ----- VIEW SOFTWARE Issue Shows the version number of the operating software. 1. 0 0 AX400/2000 Issue If optional analog output board fitted – see Section 3.5. VIEW CLOCK VIEW SOFTWARE (if optional analog output board not fitted) – see Section 2.3. Operating Page Dual Cond.
  • Page 12: Setup

    4 SETUP 4.1 Sensor Calibration Sensor Calibration Note. Applicable only if is set to – see Section 5.3. Enable Cals. ----- SENSOR CAL. Sensor Calibration Security Code Enter the required code number, between 00000 and 19999, to gain access to the sensor calibration procedure.
  • Page 13 4 SETUP …4.1 Sensor Calibration Edit Sensor Slope 100. 0 uS/cm The upper display shows the measured conductivity. The lower display shows the process sensor slope. 1. 0 00 A: Sensor Slope Adjust the slope within the valid range 0.2000 to 5.000 until the conductivity reading is correct.
  • Page 14: Programming

    5 PROGRAMMING 5.1 Security Code Enter the required code number, between 00000 and 19999, to gain access to the secure parameters. If an incorrect value is entered, access to subsequent programming pages is prevented and the display reverts to the –...
  • Page 15: Configure Display

    5 PROGRAMMING… 5.2 Configure Display ----- CONFIG. DISPLAY ----- Set Language See below. Set Temp. Units Language Page Select the language to be used on all subsequent pages. ----- English Italiano Espanol See below. Set Temp. Units Francais Deutsch Set Language ----- Set Temp.
  • Page 16: Configure Conductivity Sensors

    …5 PROGRAMMING 5.3 Configure Conductivity Sensors ----- CONFIG. SENSORS Configure Sensor A ----- Cond. Config. Sensor A Dual input conductivity only – Sensor B configuration is identical to Sensor A Config. Sensor B configuration. Single input conductivity only – return to main menu. CONFIG.
  • Page 17 5 PROGRAMMING… …5.3 Configure Conductivity Sensors _Ohms mS/m Conductivity Units mS/cm Units can be programmed to suit the range and application. Select the required units, uS/m –1 ensuring the range does not exceed the display limit of 10,000 µS cm uS/cm ----- A: Cond.Units...
  • Page 18 …5 PROGRAMMING …5.3 Configure Conductivity Sensors NaCl NaOH Temperature Compensation Select the type of temperature compensation required: Linear ----- None None – Select when raw conductivity measurement without temperature compensation is required. A: Temp.Comp. Examples • Water for injection (WFI) for US Pharmacopoeia (USP) applications. •...
  • Page 19 5 PROGRAMMING… …5.3 Configure Conductivity Sensors Temperature Sensor Select the type of temperature sensor used, Pt100 or Pt1000. Pt100 ----- Pt1000 A: Temp.Sensor Temperature Coefficient Note. Displayed only if is set to – see previous page. Temp.Comp. Linear 2. 0 0 %/°C Enter the temperature coefficient (α...
  • Page 20 …5 PROGRAMMING …5.3 Configure Conductivity Sensors Configure Sensor B (Dual Input Conductivity only) Sensor B configuration is identical to Sensor A configuration. ----- Config. Sensor B ----- B: Enable Cals. Dual input conductivity only – see below. Signal Calc. Config. Sensor B Signal Calculation (Dual Input Conductivity only) Signal Note.
  • Page 21: Configure Alarms

    5 PROGRAMMING… 5.4 Configure Alarms ----- CONFIG. ALARMS Configure Alarm 1 ----- Config. Alarm 1 Alarm 2 (and Alarms 3 and 4 if optional analog output board is fitted) Config. Alarm 2 configuration is identical to Alarm 1. Alarm 1 Type Select the type of alarm required: ----- Alarm...
  • Page 22 …5 PROGRAMMING …5.4 Configure Alarms Alarm 1 Failsafe If failsafe action is required select , otherwise select ----- A1: Failsafe Alarm 1 Action Select the alarm action required, High ----- High A1: Action Alarm 1 Set Point The alarm 1 set point can be set to any value within the input range being displayed. Set the alarm set point to the required value –...
  • Page 23 5 PROGRAMMING… …5.4 Configure Alarms Process Variable Process Variable High Set Point High Set Point Relay Energized, LED Off Relay Energized, LED On Relay De-energized, LED Off Relay De-energized, LED On Fig. 5.1 High Failsafe Alarm without Fig. 5.4 High Non–Failsafe Alarm without Hysteresis and Delay Delay and Hysteresis Process Variable...
  • Page 24: Configure Outputs

    …5 PROGRAMMING 5.5 Configure Outputs ----- CONFIG. OUTPUTS Configure Output 1 ----- Config. Output 1 Output 2 configuration (and Outputs 3 and 4 if optional analog output board Config. Output 2 is fitted) is identical to Output 1 configuration. % Pass Temp.B Assign Sen.B...
  • Page 25 5 PROGRAMMING… …5.5 Configure Outputs Span Value 100. 0 uS/cm Span value – set the required span value. 0. 0 00 uS/cm Zero value. AO1: Span Value Zero Value 100. 0 uS/cm Span value. 0. 0 00 uS/cm Zero value – set the required zero value – see Fig. 5.6. AO1: Zero Value Note.
  • Page 26: Output Functions

    …5 PROGRAMMING …5.5 Configure Outputs i t a y l l : e l v i t y t i v i t y t i Ω m v i t y t i s t i MΩ – ° ) C °...
  • Page 27: Logarithmic Output (2-Decade)

    5 PROGRAMMING… …5.6 Output Functions 5.6.2 Logarithmic Output (2-decade) – Fig. 5.7 100% Conductivity Measurement – shown as % of Analog Output Span Value Fig. 5.7 Logarithmic Output (2-Decade) 5.6.3 Logarithmic Output (3-decade) – Fig. 5.8 0.1% 100% Conductivity Measurement – shown as % of Analog Output Span Value Fig.
  • Page 28: Configure Clock

    …5 PROGRAMMING 5.7 Configure Clock Note. Available only if the optional analog output board is fitted. ----- CONFIG. CLOCK Set Clock Set the system clock. ----- Set Clock? Format Select the required clock format. ----- m m:dd:yy dd:mm:yy Format Date Set the date in the form dd:mm:yy.
  • Page 29: Configure Security

    5 PROGRAMMING… 5.8 Configure Security ----- CONFIG. SECURITY Alter Security Code Set the security code to a value between 0000 and 19999. 00000 Alter Sec. Code Alter Calibration Code Set the sensor calibration access code to a value between 0000 and 19999. 00000 Alter Cal.
  • Page 30: Test Outputs

    …5 PROGRAMMING 5.9 Test Outputs ----- TEST/MAINTENANCE Test Outputs Displays the output test details for the four channels. Test Output 1 only is shown; the remaining outputs are identical. ----- Test Outputs Note. Outputs 3 and 4 are available only if the optional analog output board is fitted. See below.
  • Page 31: Installation

    6 INSTALLATION 6.1 Siting Requirements Caution. • Mount in a location free from excessive vibration. • Mount away from harmful vapours and/or dripping fluids. Information. It is preferable to mount the analyzer at eye level, allowing an unrestricted view of the front panel displays and controls.
  • Page 32: Mounting

    …6 INSTALLATION 6.2 Mounting 6.2.1 Wall-/Pipe-mount Analyzers – Figs. 6.2 and 6.3 Dimensions in mm (in.) 94 (3.7) 210 (8.23) 192 (7.56) 96 (3.76) Fig. 6.2 Overall Dimensions 61 (2 ) OD Position 'U' bolts on pipe Vertical or Horizontal Position plate over 'U' bolts Drill suitable Post...
  • Page 33: Panel-Mount Analyzers

    6 INSTALLATION… …6.2 Mounting 6.2.2 Panel-mount Analyzers – Figs. 6.4 and 6.5 Dimensions in mm (in.) +0.8 +0.03 (3.62 –0 –0 137.50 (5.41) (0.98) 96 (3.78) +0.8 –0 Panel Cut-out +0.03 (3.62 –0 5.40 (0.2) Fig. 6.4 Overall Dimensions Cut a hole in the panel (see Fig. 6.4 for dimensions). Instruments may be close stacked to DIN 43835.
  • Page 34: Connections, General

    …6 INSTALLATION 6.3 Connections, General Warning. The power supply earth (ground) must be connected to ensure safety to personnel, reduction of the effects of RFI interference and correct operation of the power supply interference filter. Caution. The metal braid in the conductivity cell connecting cable must not be earthed, or allowed to touch earthed components, and must be cut back to the insulation at the conductivity cell end.
  • Page 35: Relay Contact Protection And Interference Suppression

    6 INSTALLATION… …6.3 Connections, General 6.3.1 Relay Contact Protection and Interference Suppression – Fig. 6.6 If the relays are used to switch loads on and off, the relay contacts can become eroded due to arcing. Arcing also generates radio frequency interference (RFI) which can result in analyzer malfunctions and incorrect readings. To minimize the effects of RFI, arc suppression components are required;...
  • Page 36: Cable Entry Knockouts Wall-/Pipe-Mount Analyzer

    …6 INSTALLATION …6.3 Connections, General 6.3.2 Cable Entry Knockouts, Wall-/Pipe-mount Analyzer – Fig. 6.7 The analyzer is supplied with 7 cable glands, one fitted and six to be fitted, as required, by the user – see Fig. 6.7. Release the captive screws and remove the terminal cover plate Factory-fitted cable gland...
  • Page 37: Wall-/Pipe-Mount Analyzer Connections

    6 INSTALLATION… Warning. Before making any connections, ensure that the power supply, any high voltage-operated control circuits and high common mode voltages are switched off. 6.4 Wall-/Pipe-mount Analyzer Connections 6.4.1 Access to Terminals – Fig. 6.8 Release Captive Screws and Remove Terminal Cover Plate Terminal Block C (Analog Option Board)
  • Page 38: Connections

    …6 INSTALLATION …6.4 Wall-/Pipe-mount Analyzer Connections 6.4.2 Connections – Fig. 6.9 Terminal Block C (Analog Option Board) Terminal Block B Temperature Compensator Temperature Compensator Connections Connections Terminal block A Terminal Block B Sensor B* Sensor A Conductivity Cell Connections TC Common, Link B1 to B2 (Dual Conductivity Only) / B9 to B10** TC Third Lead Screen Cell (Cell Electrode)
  • Page 39: Panel-Mount Analyzer Connections

    6 INSTALLATION… Warning. Before making any connections, ensure that the power supply, any high voltage-operated control circuits and high common mode voltages are switched off. 6.5 Panel-mount Analyzer Connections 6.5.1 Access to Terminals – Fig. 6.10 Terminal Block A Earth (Ground) Stud Terminal Block C Terminal Block B (Analog Option Board)
  • Page 40: Connections

    …6 INSTALLATION …6.5 Panel-mount Analyzer Connections 6.5.2 Connections – Fig. 6.11 Terminal block A Terminal Block C Terminal Block B (Analog Option Board) Line Common Neutral Third Lead Earth (Ground) Temperature Compensator Connections Relay 1 Earth (Ground) Relay 2 Relay 4 Common A10 C C10 C...
  • Page 41: Calibration

    7 CALIBRATION ✶ Notes. • The analyzer is calibrated by the Company prior to dispatch and routine recalibration is not necessary. High stability components are used in the analyzer's input circuitry and, once calibrated, the Analog to Digital converter chip self- compensates for zero and span drift.
  • Page 42: Factory Settings

    …7 CALIBRATION 7.3 Factory Settings Use the Sidescroll Key to scroll through the Pages within each Menu Section 7.3, Page 41 FACTORY SETTINGS Factory Set Code Cal. Sensor A Cal. Sensor B Cal. Output 1 A:Res.Zero (O/C) B:Res.Zero (O/C) O1: Adjust 4mA Use the Menu A:Res.Span (2K0) B:Res.Span (2K0)
  • Page 43 7 CALIBRATION… …7.3 Factory Settings ----- FACTORY SETTINGS Factory Settings Access Code Enter the required code number, between 00000 and 19999, to gain access to the factory settings. If an incorrect value is entered, access to subsequent parameters is prevented 0000 and the display reverts to the top of the Factory Settings Page...
  • Page 44 …7 CALIBRATION …7.3 Factory Settings Resistance Span (20 ) 2. 0 15 Volts Set the cell simulator to 20 2. 0 15 Calib The display advances automatically to the next step once a stable and valid value is A:Res.Span(20R0) recorded. Resistance Reference Voltage 2.
  • Page 45 7 CALIBRATION… …7.3 Factory Settings Calibrate Output 1 ✶ Note. When adjusting the 4 and 20mA outputs, the display reading is unimportant ----- and is used only to indicate that the output is changing when the keys are pressed. Cal. Output 1 See below.
  • Page 46 …7 CALIBRATION …7.3 Factory Settings Load/Save Configuration Select whether a configuration is to be loaded or saved. ✶ ----- Note. If is selected, pressing the key has no effect. Load/Save Config See below. Alter Fact. Code Return to Operating Page Dual Cond.
  • Page 47: Simple Fault Finding

    8 SIMPLE FAULT FINDING 8.1 Error Messages b) If the response in a) is correct, reconnect the conductivity cell cable and connect the resistance box to the cell end. If erroneous or unexpected results are obtained the fault may be indicated by an error message –...
  • Page 48: Appendix A

    APPENDIX A A1 Automatic Temperature Compensation At high purity water conductivity levels, the conductivity/ temperature relationship is made up of two components: the The conductivities of electrolytic solutions are influenced considerably by temperature variations. Thus, when significant first component, due to the impurities present, generally has a temperature fluctuations occur, it is general practice to correct temperature coefficient of approximately 0.02/°C;...
  • Page 49: A1.1 Calculation Of Temperature Coefficient

    APPENDIX A… A1.1 Calculation of Temperature Coefficient The temperature coefficient of a solution can be obtained experimentally by taking non-temperature compensated conductivity measurements at two temperatures and applying the following expression: – G ∝ = – 25) – G – 25) Where: G = conductivity measurement at a temperature of t...
  • Page 50: A3 Inferred Ph Derived From Differential Conductivity

    …APPENDIX A A3 Inferred pH Derived from Differential Conductivity Where cation resin columns are used to remove the effects on the conductivity measurement of alkaline and hydrazine chemical treatment on boilers, it is common practice to measure both before- (specific conductivity) and after-cation conductivity. The sensitivity of the conductivity measurement to chemical contaminants resulting from condenser leaks or poor boiler-feed make-up water is increased by passing the sample through the...
  • Page 51: Specification

    SPECIFICATION Conductivity Range Emissions and immunity Programmable 0 to 0.5 to 0 to 10000 µS/cm Meets requirements of: (with various cell constants) EN61326 (for an industrial environment) Units of measure EN50081-2 µS/cm, µS/m, mS/cm, mS/m, M -cm and TDS EN50082-2 Accuracy Analog Retransmission Better than ±1% of reading...
  • Page 52 …SPECIFICATION Relay Outputs Mechanical Data Panel-mount versions Number of relays IP66/NEMA4X Three, supplied as standard Dimensions 192mm high x 230mm wide x 94mm deep Five, when ordered with option card (7.56 in. high x 9.06 in. wide x 3.7 in. deep) Set point adjustment Weight 1kg (2.2 lb) Fully programmable...
  • Page 53 NOTES...
  • Page 54 …NOTES...
  • Page 55 – Manufacturing United Kingdom – Metals and Minerals – Oil, Gas & Petrochemical ABB Limited – Pulp and Paper Tel: +44 (0)1453 826661 Fax: +44 (0)1453 827856 Drives and Motors United States of America • AC and DC Drives, AC and DC Machines, AC motors to 1kV ABB Inc.
  • Page 56 ABB has Sales & Customer Support The Company’s policy is one of continuous product improvement and the right is reserved to modify the expertise in over 100 countries worldwide information contained herein without notice. www.abb.com Printed in UK (06.02) © ABB 2002 ABB Limited ABB Inc.

Table of Contents