5.8.1 Configure Single PID Controller

Controller
set to
PID
----
PID Controller
Rev.
----
Direct
Control Action
100. 0
% Man
Prop. Band
100
Secs
Integral Time
10. 0
Secs
Derivative Time
Pulse
Analog
Time
----
Output Type
IM/AX4CO
Issue 11
See Section 5.8.2.
Power Recovery
Control Action
Set the required control action:
Rev.
Direct
Proportional Band
Set the required proportional band, between 0.0 and 999.9% in 0.1% increments.
Integral Action Time
Set the integral action time, between 1 and 7200 seconds in 1 second increments.
Set to
to disable integral action time.
OFF
Derivative Action Time
Set the derivative action time, between 0.1 and 999.9 seconds in 0.1 second
increments.
Set to OFF to disable derivative action time.
Output Type
Set the required output type:
Time
Analog
Pulse
set to
Cycle Time
Output Type
set to
Output Range
Output Type
set to
Pulses/Minute
Output Type
-
Reverse acting - see appendix B on page 78, Fig. B.2.
-
Direct acting - see appendix B on page 78, Fig. B.3.
-
Time proportioning (relay 1)
-
Analog output (analog output 1)
-
Pulse frequency (relay 1)
- continued on next page.
Time
- continued on next page.
Analog
- continued on page 45.
Pulse