Panel-Mount Analyzer Connections; Connections - ABB AX410 User Manual

Single and dual input analyzers for low level conductivity
Hide thumbs Also See for AX410:
Table of Contents

Advertisement

...6.5 Panel-mount Analyzer Connections

6.5.2 Connections – Fig. 6.11
Terminal block A
85 to 265 V AC +
L
Line
or
N
Neutral
24 V AC
E
Connect supply earth (ground) to stud on case
A4 C
A5 NC
Relay 1
A6 NO
A7 C
A8 NC
Relay 2
A9 NO
A10 C
A11 NC
Relay 3 (see Note 1 below)
A12 NO
A13 +
Analog Output 1
A14 —
A15 +
Analog Output 2
A16 —
Before making any electrical
connections, see Warnings
on page 53
Notes.
• When connecting non-metal conductivity cells or metal conductivity cells that are isolated from earth (ground), e.g.
mounted in plastic pipework, link Terminal B14 (and Terminal B6 if dual input analyzer) to the earth (ground) stud on
the analyzer case – see Fig. 6.10.
• When connecting earthed (grounded) metal conductivity cells, ensure that the cell earth (ground) and the analyzer
earth (ground) stud are at the same potential.
Terminal Block C
12
Power
to
Supplies
24V DC
Earth (Ground)
Stud on Case
(see Fig. 6.10)
Terminal Block B
Sensor B
Sensor A
B1
B9
B2
B10
B3
B11
B4
B12
B5
B13
B6
B14
B7
B15
B8
B16
* When a 2-wire Pt100, Pt1000 or 'balco 3k' temperature compensator is fitted.
Refer also to Section 6.6 for ABB UK and US Sensor Systems Connections
Fig. 6.11 Connections, Panel-mount Analyzers
(Option Board)
C1
Not Used
C2
Not Used
C3
Used for optional
RS485 connection.
C4
Refer to IM/PROBUS
C5
C6
Not Used
C7
C
C8
NC
Relay 4
C9
NO
C10 C
C11 NC
Relay 5
C12 NO
C13 +
Analog Output 3
C14 —
C15 +
Analog Output 4
C16 —
Conductivity Cell Connections
Temperature Compensator Common.
Link B9 to B10 (and B1 to B2 if Dual Input Analyzer) *
Temperature Compensator Third Lead
Temperature Compensator
Cell (Cell Electrode)
Cell (Earth Electrode) – see Note below
Not Used
Not Used
6 INSTALLATION...
Terminal Block B
Common
Link
TC
Temperature Compensator

Connections

Common
Link
TC
Temperature Compensator
Connections
Screen
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
59