5.2
Internal User Devices
Internal user devices can be used for various user applications.
(1) Points for internal user devices
Set the number of device points to be used.
Project window [Parameter] [PLC Parameter] [Device]
When changing device points, note the following.
• The points for the input (X), output (Y) cannot be changed.
• Set each device in increments of 16 points.
• Up to 29K words can be set for total internal user devices.
• The maximum number of points for a bit device is 32K. For an internal relay and link relay, the maximum
number of points can be set up to 60K.
• One point of the timer, retentive timer, and counter is regarded as one word device point and two bit device
points. ( Page 291, Section 5.2 (2))