Restoring Backup Data - Mitsubishi Electric L02SCPU User's Manual And Reference

Melsec-l series, cpu module
Table of Contents

Advertisement

3.28.2

Restoring backup data

Backup data are automatically restored when:
• the CPU module is powered off and then on or
• the CPU module is reset.
Whether to restore data once after backup or per above operation can be set by on/off of SM676.
Status of SM676
SM676 = OFF
SM676 = ON
After backup data are restored, the BAT.LED on the CPU module turns on (green) for five seconds.
If the number of device points at the time of parameter configuration are different from those at backup, "RESTORE
ERROR" (error code: 2220) is detected upon restoration, and the restoration cannot be completed. (Restoration is
performed again when the CPU module is powered off and then on or is reset the next time.) To complete the restoration,
perform any of the following operations.
• Set the parameters back to the configuration before backup.
• Delete the backup data.
• Back up the data again.
Data are restored once when the CPU module is powered off and then on or is reset after backup.
Data are restored whenever the CPU module is powered off and then on or is reset after backup. Data are repeatedly
restored until the backup data are deleted or the latch data are backed up next time.
CHAPTER 3 CPU MODULE FUNCTIONS
Restoration operation
3