(2) Commands
The following table lists the MC protocol commands that can be executed.
Function
In units of
bits
Batch read
In units of
words
In units of
bits
*1
Batch write
In units of
words
Random
In units of
*2*3
words
read
Device
memory
In units of
bits
*1
Test
(random
In units of
write)
words
Monitor
In units of
*2
registration
words
*3*4
In units of
Monitor
words
*1
To perform online change, check the "Permit" checkbox under "Online Change".
*2
Devices such as TS, TC, SS, SC, CS, and CC cannot be specified in units of words.
For the monitor registration, an error (4032
*3
The monitor condition specification cannot be used for these commands.
*4
Do not execute monitor registration from multiple external devices. If executed, the last monitor registration becomes
valid.
*5
Set the number of processing points within the range of the following calculation formula.
(number of word access points) 12 + (number of double word access points) 14 960
• One point of a bit device corresponds to 16 bits for word access or to 32 bits for double word access.
• One point of a word device corresponds to one word for word access or to two words for double word access.
Command
0401 (001)
Reads out a bit device in units of one point.
Reads out a bit device in units of 16 points.
0401 (000)
Reads out a word device in units of one point.
1401 (001)
Writes into a bit device in units of one point.
Writes into a bit device in units of 16 points.
1401 (000)
Writes into a word device in units of one point.
Reads out a bit device in units of 16 or 32 points by
specifying a device/device number at random.
0403 (000)
Reads out a word device in units of one or two
points by specifying a device/device number at
random.
Sets/resets a bit device in units of one point by
1402 (001)
specifying a device/device number at random.
Sets/resets a bit device in units of 16 or 32 points
by specifying a device/device number at random.
1402 (000)
Writes into a word device in units of one or two
*2
points by specifying a device/device number at
random.
Registers a bit device to be monitored in units of 16
or 32 points.
0801 (000)
Registers a word device to be monitored in units of
one or two points.
0802 (000)
Monitors a device registered.
) occurs during the monitor operation.
H
CHAPTER 3 CPU MODULE FUNCTIONS
Description of processing
Number of
processing points
• ASCII: 3584 points
• BIN: 7168 points
480 words (7680 points)
480 points
• ASCII: 3584 points
• BIN: 7168 points
480 words (7680 points)
480 points
96 points
94 points
*5
96 points
96 points
Number of monitor
registration points
229