(b) When only a device is specified
Either word device or bit device can be specified.
• When a word device is specified
Monitor data is collected when the current value of the specified word device becomes the specified value.
Specify the current value in decimal or hexadecimal.
• When a bit device is specified
Monitor data is collected when the execution status of the specified bit device becomes the specified status.
Select the execution condition (on the rising edge or falling edge).
(c) When a step number and device are specified
Monitor data is collected when the status immediately before execution of the specified step becomes the
specified status or the status (current value) of the specified bit device (word device) becomes the specified
value.
If the rise of step 100 and D1 = 5 (Step No. [100] = <>, Word device [D1] = [K5]) are specified as the execution condition,
the monitor execution condition is established on the rising edge of the step 100 and also D1=5.
X0
M0
The monitor interval of a programming tool depends on the processing speed of the programming tool. For the monitor
execution conditions established at the interval shorter than the monitor interval of the programming tool, monitor is
executed only when the monitor execution condition is established at the monitor timing of the programming tool.
Step No.
M0
X0
D1=5
Monitor timing
(CPU module)
100
100
CHAPTER 3 CPU MODULE FUNCTIONS
Step 100
Y20
INC D1
100
100
3
125