(13) Built-in Serial Setting
Parameters required for data communications using the predefined protocol function or the serial communication
function via the RS-232 interface of the CPU module are set.
Remark
The setting is available only for the L02SCPU and L02SCPU-P.
Parameter No.
Item
Select Function
Data Bit
Parity Bit
Not Used
Odd/Even
Parity
Stop Bit
370
Description
Select the function to be used.
Set the data bit.
• For serial
communication
: 100E
Set the parity bit.
H
• For predefined
protocol:
Select either odd parity or even
101B
H
parity. (Setting is available only
when the parity bit is set to
"Include".)
Set the stop bit.
Setting range
• Not Used
• Serial Communication
• Predefined Protocol
• 7
• 8
For the serial communication
function, this is fixed to "8".
• Not include
• Include
For the serial communication
function, this is fixed to "Include".
• Odd
• Even
For the serial communication
function, this is fixed to "Odd".
• 1
• 2
For the serial communication
function, this is fixed to "1".
Default
Reference
Not Used
8
Page 215,
Include
Section 3.37
Page 227,
Section 3.38
Odd
1