7.4.5 Core changeover

Selection method
Replacement value
for probe break
Signal 1 — 4
IMAGO F3000 / 10.01
Up to 4 temperature sensors can be used to acquire the core temperature.
The following methods are available:
Selection/settings
None
Minimum of signals 1—4
Maximum of signals 1—4
First valid measurement from
signals 1—4
Average of signals 1—4
Error message
Chamber process value
(Analog selector)
1
OFF
2
Analog input 3
k
/ bold = factory setting
1. factory settings for signals 2 — 4
2. factory setting for signal 1
7 Setup Program
Description
No selection; output is the replacement value.
Minimum of signals 1—4:
The smallest value measured counts as the core
temperature.
Maximum of signals 1—4:
The largest value measured counts as the core
temperature.
First valid measurement from signals 1—4:
If one or more probes have a fault, then the next
valid measurement is taken as the core
temperature (sequence: signal 1 — signal 4).
An average is formed, and this is then used as the
core temperature measurement.
The replacement value can either be a value that is
output to replace the missing core temperature, or
an error message.