Contents Preface ............... 3 Scope of delivery ..............3 Identifying the instrument version ....4 Mounting ............5 Preparation ................5 Fitting in position, Type 703042/43/44 ........5 Fitting in position, Type 703041 ..........5 Electrical connection ........6 Connection diagram for Type 703041 ........6 Connection diagram for Type 703042/43/44 ......
The factory settings for the instrument as delivered are shown on a rastering gray background. The complete configuration options can be found in the comprehensive Operating Manual B 70.3041.0 on the CD, or can be downloaded from http://www.jumo.net Scope of delivery - 1 controller - seal - mounting brackets...
1 analog input, 2 relay outputs and 2 binary inputs or 2 logic outputs 703042 JUMO dTRON 308, 48 mm x 96 mm format (portrait format) incl. 1 analog and 2 binary inputs, 2 relays and 2 logic outputs 703043 JUMO dTRON 308, 96 mm x 48 mm format (landscape format) incl.
3 Mounting Mounting Preparation Type dTRON Panel cut-out +0.6 +0.6 703041 316, in 48 mm x 48 mm format x 45 +0.8 +0.8 703042/43 308, in 48 mm x 96 mm format x 92 (portrait)/(landscape) +0.8 +0.8 703044 304, in 96 mm x 96 mm format x 92 Fitting in position, Type 703042/43/44 h Fit the seal that is supplied onto the instrument...
6 Operation Operation Level concept The diagram below shows the three instrument levels. Time-out If no key is pressed for 30 sec, the instrument returns to normal display.
6 Operation Level inhibit The access to the individual levels can be inhibited by entering a code number. h Press simultaneously for >5 sec to enter the code. Code Operator level Parameter level Configuration level enabled enabled enabled enabled enabled inhibited enabled inhibited...
6 Operation Entering times When entering times (e.g. time of timer), the time unit is shown in addition. Select Alter parameter parameter I I I I I I I I I I I I I The highest time unit of the display is shown for the unit. For example, if “h”...
6 Operation Operation of the fixed-setpoint controller The fixed-setpoint controller will only function if - the fixed-setpoint controller function has been configured ( Fnct = 0) Normal display Manual mode h Alter the present setpoint The controller output appears in the with lower display.
6 Operation Operation of the program controller The program controller will only function if - the program controller function has been configured ( Fnct = 1 ...4) - the program setpoints (SPP1 ... SPP8) and segment times (tP 1 ... tP 8) have been entered Normal display Program is running (the symbol for ramp appears)
7 Operator level “OPr” Operator level “OPr” Process data ProC Symbol Meaning SP 1 Setpoint 1 (editable) SP 2 Setpoint 2 (editable) SP 3 Setpoint 3 (editable) SP 4 Setpoint 4 (editable) Ramp setpoint (only if configured) InP1 Measurement of analog input 1 InP2 Measurement of analog input 2 (only if available) Calculated result of math formula 1 (only if available)
8 Parameter level “PArA” Parameter level “PArA” Two parameter sets, PAr1 und PAr2, can be stored. Parameter Symbol Value range Factory setting Proportional band 1 Pb 1 0 ... 9999 °C/°F 0 °C/°F Proportional band 2 Pb 2 0 ... 9999 °C/°F 0 °C/°F Derivative time 0 ...
9 Configuration level “ConF” Configuration level “ConF” Depending on the equipment level of the instrument, individual parameters or groups of parameters are switched out of display. Analog selector With some parameters, you can choose from a series of analog signals. The list below gives you an overview of the selection options.
9 Configuration level “ConF” Linearization 0 Linear 10 Thermocouple type U 1 Pt100 11 Thermocouple type L 2 Pt500 12 Thermocouple type K 3 Pt1000 13 Thermocouple type S 4 KTY11-6 14 Thermocouple type R 5 Thermocouple type C 15 Thermocouple type B 6 Thermocouple type D 16 Thermocouple type N 7 Thermocouple type E...
9 Configuration level “ConF” r Binary outputs OutL r Output 1 — 10 Out1 ... Out0 r Function 0 no function 16 Limit comparator 4 1 Controller output 1 17 Control contact 1 2 Controller output 2 18 Control contact 2 3 - not used 19 Control contact 3 4 - not used...
10 Autotuning 10 Autotuning The autotuning facility can be used to automatically adapt the controller parameters to the process. The autotuning function determines the controller parameters for a PID controller or, if dt=0 is set, for a PI controller in a closed control loop. h Start with (press simultaneously for >2 sec) “tUnE”...
11 Alarms 11 Alarms Display Cause Clear faults check/rectify/replace -1999 Underrange for the value being Is the medium to be (blinking!) displayed. measured within the range (too hot - too cold?) 9999 Overrange for the value being (blinking!) Check probe for probe displayed.