12
TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
413A
H
413B
H
File-related
413C
H
errors
File-related
413D
H
errors
413E
H
413F
H
Intelligent
414A
function
H
module
specification
414C
H
error
4150
H
File-related
errors
4151
H
4160
H
4165
H
4166
H
Online
4167
H
registration
error
4168
H
4169
H
416A
H
416B
H
12
- 230
12.3 Error Code List
12.3.11 Error codes returned to request source during communication with CPU module
Table12.12 Error code
Error details
The specified file has exceeded the already
existing file size.
The same file was accessed simultaneously
from different peripheral devices.
The specified file is write-inhibited.
The specified file capacity cannot be secured.
Operation is disabled for the specified drive
(memory).
The file is inhibited from write to the standard
RAM.
Operation was executed for the intelligent
function module of the non-control group in the
multiple CPU system.
The I/O address of the specified CPU module
is wrong.
An attempt was made to format the drive
protected by the system.
An attempt was made to delete the file
protected by the system.
The registered number of forced inputs/
outputs exceeded the maximum value.
The multiple-block online change system file
does not exist.
Cannot be executed since file batch online
change is being made by the same starting
source.
Cannot be executed since file batch online
change is being made from the other starting
source.
The registered number of device test with
executing condition exceeds 32.
The device test with executing condition has
never been registered.
The specified executing condition does not
exist.
(Device test with executing condition)
The specified program is SFC program.
(Device test with executing condition)
Corrective action
Execute again after checking the size of the specified
file.
Execute again after a while.
Execute again after changing the file condition.
Execute again after increasing the capacity of the
specified drive (memory).
Execute again after changing the target drive (memory).
Execute again after changing the specified drive
(memory).
Execute the operation again from the control CPU of the
target module.
Execute again after checking the I/O address of the
specified CPU module.
Do not format the target drive (memory) as it cannot be
formatted.
Do not delete the target file as it cannot be deleted.
Deregister the unused forced inputs/outputs.
Execute again after securing the area that enables
multiple-block online change at the time of
programmable controller memory format.
Since the file batch online change executed previously
remains abnormally terminated for some reason
(example: communication disturbance during execution),
file batch online change is disabled.
Forcibly perform new file batch online change.
Since the file batch online change executed previously
from the other communication route remains abnormally
terminated for some reason (example: communication
disturbance during execution), file batch online change is
disabled.
If file batch online change is not being executed by the
other peripheral device, forcibly perform new file batch
online change.
Deregister the device test with executing condition in
CPU module, or decrease the number of registering
device test with executing condition at one time.
Deregister the device test with executing condition after
checking the registered number of device test with
executing condition in CPU module.
Check whether the specified executing conditions
(program, step No. operation timing, device name) in
deregistering are registered.
Check the specifing program name in de/registering the
device test with executing condition.