When Battery Has Gone Flat During Storage Of Programmable Controller - Mitsubishi Q01CPU User Manual

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

11
MAINTENANCE AND INSPECTION
11.5 When Battery Has Gone Flat During Storage of Programmable
Controller
When the programmable controller is to be used after being stored for some period of time
and the battery has gone flat during storage, the memories in the CPU module and
memory card may be corrupted.
Hence, before resuming operation, always clear the memory of CPU module and format
the SRAM card using GX Developer.
After formatting the memories, write the memory contents backed up prior to storage to
each memory.
Remark
The relationships between battery and battery-backed memorie are shown in Table11.15.
CPU module
Memory card
Format the battery-backed memories in Table11.15 using GX Developer before resuming
operation.
For information about the memory formatting, refer to the manual below.

11.5 When Battery Has Gone Flat During Storage of Programmable Controller

For the Universal model QCPU, when the latch data backup function (to standard
ROM) is used, data will not be disappeared even if a battery life ends, since latch
data such as device data of the CPU module or error history can be backed up
without using a battery.
Table11.15 Relationships between the battery and battery-backed memories
Memory
Program memory
Standard RAM
Standard ROM
SRAM card
*3
Flash card
ATA card
* 1: As a battery, the Q6BAT, Q7BAT and Q8BAT are available.
* 2: The Universal model QCPU needs no battery backup.
* 3: Not available for the Basic model QCPU.
GX Developer Operating Manual
Battery
Battery of QCPU
Battery Built in Memory
*1
Module
*2
---- (Battery backup not needed)
---- (Battery backup not needed)
---- (Battery backup not needed)
: Battery backed,
9
10
11
12
Card
: Not battery backed