Mitsubishi Q01CPU User Manual page 525

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
• An error (e.g. retry limit exceeded)
occurred in tracking (data
transmission).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
6105
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
• A timeout error occurred in tracking
(data transmission).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
6106
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
A data sum value error occurred in
tracking (data reception).
6107
(This can be detected from the control
system or standby system of the
redundant system.)
• A data error (other than sum value
error) occurred in tracking (data
reception).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
6108
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
The tracking capacity exceeded the
allowed range.
6110
(This can be detected from the control
system or standby system of the
redundant system.)
*1
The module whose first 5 digits of serial No. is 09012 or later.
Corrective Action
• Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or tracking
cable is faulty. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup
again.
• Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or tracking
cable is faulty. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup
again.
Reexamine the tracking capacity.
12.3 Error Code List
12.3.8 Error code list (6000 to 6999)
9
Corresponding
CPU
10
11
QnPRH
12
QnPRH
QnPRH
12
- 201