4
HARDWARE SPECIFICATIONS OF THE CPU MODULE
No.
Name
5)
RUN LED
6)
ERR. LED
7)
Module connector
DIN rail adaptor mounting
8)
holes
9)
FG terminal
10)
LG terminal
11)
Power input terminals
12)
Battery
Battery fixing
13)
hook
14)
Battery connector pin
15)
RS-232 connector
16)
RUN/STOP/RESET switch
4
- 22
4.2 Basic Model QCPU
4.2.1 Part Names
Indicates the operating status of the CPU module.
ON
: During operation with the RUN/STOP/RESET switch set to "RUN".
OFF
: During stop with the RUN/STOP/RESET switch set to "STOP"
Flicker : When parameters/program is written during STOP and the RUN/STOP/
RESET switch is moved from "STOP" to "RUN".
To turn ON the RUN LED after writing the program, carry out the following
steps.
•Move the RUN/STOP/RESET switch from "RUN" to "STOP" to "RUN".
•Perform reset with the RUN/STOP/RESET switch.(
•Power ON the programmable controller again.
To turn ON the RUN LED after writing the parameters, carry out the
following steps.
•Perform reset with the RUN/STOP/RESET switch.
•Power ON the programmable controller again.
(If the RUN/STOP/RESET switch is moved from "STOP" to "RUN" to
"STOP" to "RUN" after changing the parameter values, the new values are
not reflected on the parameters related to the intelligent function module,
such as the network parameters.)
ON
: When the self-diagnostic error that will not stop operation is detected.
•When continuation of operation at error detection is set in the parameter.
•When the annunciator (F) is turned ON by the SET/OUT instruction.
•When battery low occurs.
OFF
: Normal
Flicker : When the error whose occurrence stops operation is detected.
When reset operation is performed with the RUN/STOP/RESET switch.
Connector used for loading an input/output or intelligent function module.
(To the connector of the spare space where no module is loaded, fit the accessory
connector cover or the blank cover module (QG60) to prevent dust from entering.)
Holes for mounting a DIN rail adaptor.
Ground terminal connected with the shield pattern of the printed circuit board.
Power filter ground having a half potential of the input voltage.
Power input terminals for connection of a 100VAC to 200VAC power supply.
Backup battery for use of the program memory, standard RAM, timer function and
power failure compensation function.
Hook for holding the battery.
For connection of the battery lead wires.
(When shipped from the factory, the lead wires are disconnected from the connector
to prevent the battery from consuming.)
Connector for connecting a peripheral device by RS-232.
*1
Can be connected by the RS-232 connection cable (QC30R2).
RUN
: Executes sequence program operation.
STOP : Stops sequence program operation.
*2
RESET : Performs hardware reset, operation error reset, operation initialization or
like. (
Table4.6 Part Names
Application
Section 4.2.3)
Section 4.2.3)