LOADING AND INSTALLATION
(1) System design circuit example (when not using ERR terminal of power
Power supply
START SW
MC
Output module
Output module
MC
The power-ON procedure is as follows:
For AC
1) Turn power ON.
2) Set CPU to RUN.
3) Turn ON the start switch.
4) When the magnetic contactor (MC) comes
ON, the output equipment is powered and
may be driven by the program.
supply module, or using Q00JCPU)
FOR AC
Transformer
Input switched when
power supply
Fuse
established.
CPU module
RUN/STOP circuit
SM52
Ym
interlocked with RA1
(run monitor relay)
SM403
Yn
Program
RA1
MC
STOP SW
Input module
Low battery alarm
(Lamp or buzzer)
Ym
L
ON when run by
Yn
SM403
RA1
MC
Power to output
equipment switched
OFF when the STOP
signal is given.
In the case of an
emergency stop or a
MC2
stop caused by a limit
MC1
switch.
MC1
Interlock circuits as
MC2
necessary.
Provide external
interlock circuits for
conflicting operations,
such as forward rotation
and reverse rotation,
and for parts that could
damage the machine or
cause accidents if no
interlock were used.
Diagram 10.1 System design circuit example
For AC/DC
1) Turn power ON.
2) Set CPU to RUN.
3) When DC power is established, RA2 goes ON.
4) Timer (TM) times out after the DC power reaches 100%. (The TM set
value should be the period of time from when RA2 goes ON to the
establishment of 100% DC voltage. Set this value to approximately 0.5
seconds.)
5) Turn ON the start switch.
6) When the magnetic contactor (MC) comes ON, the output equipment is
powered and may be driven by the program. (If a voltage relay is used at
RA2, no timer (TM) is required in the program.)
Power supply
FOR AC/DC
Transformer
Transformer
Fuse
Fuse
CPU module
SM52
DC power
Ym
SM403
Yn
XM
TM
TM
MC1 NO M10
NO
M10
Program
START SW
RA1
MC
MC
STOP SW
RA2
XM
Output module
Ym
L
Yn
RA1
Output module
MC2
MC1
MC1
MC2
10.1 General Safety Requirements
(-) (+)
Fuse
Set time for DC power
supply to be
established.
RA2
Voltage relay is
recommended
Low battery alarm
(Lamp or buzzer)
ON when run by SM403
MC
MC
Power to output
equipment switched
OFF when the STOP
signal is given.
In the case of an
emergency stop or a
stop caused by a limit
switch.
10
- 3