Mitsubishi Q01CPU User Manual page 184

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

5
POWER SUPPLY MODULE
A1S61PN
9)
3)
4)
5)
7)
No.
Name
1)
POWER LED
2)
+24V, 24G terminals
3)
FG terminals
4)
LG terminals
5)
Power input terminals
6)
Power input terminals
7)
Terminal screw
8)
Terminal cover
9)
Module fixing screw hole
5
- 30
5.3 Names of Parts and Settings
A1S62PN
1)
8)
2)
3)
Diagram 5.8 Power supply module
Table5.20 Part Names
ON (green)
: Normal (5VDC output, momentary power failure within 20ms)
OFF
: • AC power supply is ON, however, the power supply module is out of
• AC power supply is not ON
• Power failure (including an momentary power failure of 20ms or
Used to supply 24VDC power to inside the output module (using external wiring).
Ground terminal connected to the shield pattern of the printed circuit board.
Grounding for the power supply filter. The potential of A1S61PN or A1S62PN
terminal is 1/2 of the input voltage.
Used to connect a 100VAC to 200VAC power supply.
Used to connect a 24VDC power supply.
M3.5 7 screw
Protective cover of the terminal block
Used to fix the module to the base unit.
(M4 screw, tightening torque : 0.66 to 0.89N•m)
POINT
1. Do not wire to those terminals for which NC is stamped on the terminal block.
2. Ensure that the ground terminals LG and FG are grounded.
9)
1)
8)
4)
5)
7)
Application
order.
(5VDC error, overload, internal circuit failure, or fuse blown)
more)
A1S63P
9)
1)
8)
3)
4)
6)
7)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents