12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
In a multiple CPU system, the link direct
device (J \ ) was specified for the
network module under control of
another station.
• The network No. or station No.
specified for the dedicated instruction
is wrong.
4102
• The link direct device (J \ ) setting
is incorrect.
• The module No./ network No./number
of character strings exceeds the
range that can be specified.
• The specification of character string
(" ") specified by dedicated instruction
cannot be used for the character
string.
The configuration of the PID dedicated
4103
instruction is incorrect.
The number of settings is beyond the
4104
range.
PLOADP/PUNLOADP/PSWAPP
4105
instructins were executed while setting
program memory check.
33 or more multiple CPU dedicated
instructions were executed from one
4107
CPU module.
Numbers of execution to the CC-Link
instruction are beyond 32.
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07012 or later.
*5
The module whose first 5 digits of serial No. is 07032 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
*8
This applies to the QnUDE(H)CPU.
Corrective Action
• Delete from the program the link
direct device which specifies the
network module under control of
another CPU.
• Using the link direct device, specify
the network module under control of
the host CPU.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
Read the common information of the
error using peripheral device, and check
and correct the program corresponding
to that value (program error location).
• Delete the program memory check
setting.
• When using the program memory
check, delete PLOADP/PUNLOADP/
PSWAPP instructions.
Using the multiple CPU dedicated
instruction completion bit, provide
interlocks to prevent one CPU module
from executing 33 or more multiple CPU
dedicated instructions.
Set the numbers of execution to the
CC-Link instruction to 32 or less.
12.3 Error Code List
12.3.6 Error code list (4000 to 4999)
9
Corresponding
CPU
*2
Q00/Q01
10
*2
Qn(H)
QnPH
QnU
11
Rem
12
QnU
QnA
Q00J/Q00/
*2
Q01
Qn(H)
QnPRH
QnU
Q4AR
*5
QnPH
*2
Q00/Q01
*2
Qn(H)
QnPH
Q02U
QnA
12