12.2.24 Flowchart for when PARAMETER ERROR occurs at power ON/
The following shows the flowchart for when PARAMETER ERROR occurs at power ON/
reset.
(1) Flowchart for when PARAMETER ERROR (error code: 3013) occurs
The PARAMETER ERROR
(error code: 3013) has occurred.
Read the PLC parameter from the
parameter-valid drive on GX
Developer.
Check the parameter on GX
Developer.
Is the error
detected as the result of the
parameter check on GX
Developer?
NO
Is a device set
for each CPU transmission
range individually with
the multiple CPU
refresh setting?
NO
Switch the power from OFF to ON or
reset, after writing the PLC parameter
to the CPU module again.
Confirm that the same error does not
occur.
12
- 30
12.2 Troubleshooting

12.2.24 Flowchart for when PARAMETER ERROR occurs at power ON/reset.

reset.
YES
Correct the item where the error has
occurred. Perform the parameter
check on GX Developer again and
confirm that no error is detected.
YES
the transmission range for the
Set the refresh source device of the
transmission range for the host CPU
set as other than " "(Blank).
(The refresh source device of the
transmission range for the host CPU
cannot be set as " "(Blank).)
Is a device
for each refresh of
host CPU set as " "
(Blank)?
YES
YES
NO
Check the product information of the
CPU module on the GX Developer
system monitor.
Is the product
information of the CPU
module "070320000000000"
or later?
NO
Uncheck "Set starting device for each
PLC" or change to a CPU module of
which product information is
"070320000000000" or later. (If the
product information is not
"070320000000000" or later, the
function for setting a device of each
transmission range individually cannot
be used.)