Mitsubishi Q01CPU User Manual page 101

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

2
SYSTEM CONFIGURATION
(b) When the High Performance model QCPU or Process CPU is used
Q series CC-Link IE controller
network module
Q series MELSECNET/H network
module
Q series Ethernet interface module
Q series CC-Link system master
local module
MELSECNET/MINI-S3 data link
module
Special function module for the AnS
series
Interrupt module
GOT
Table2.11 Number of modules loaded
Applicable module
*3
*5
(When GET/PUT service is
*5
used)
* 3: Only High Performance model QCPU whose serial No. (first five digits) is "09012" or later and
Process QCPU whose serial No. (first five digits) is "10042" or later can be used.
* 4: The following number of modules per CPU can be controlled with the CC-Link network parameter
setting by GX Developer.
• The CPU module whose first 5 digits of serial number is "08031" or earlier: Up to four modules
• The CPU module whose first 5 digits of serial number is "08032" or later: Up to eight modules
If the parameters are set up by CC-Link dedicated instructions, the number of modules installed is
not limited.
For the CC-Link system master/local modules whose parameters can be set up by dedicated
instructions, refer to the manual below.
CC-Link System Master/Local Module User's Manual
* 5: This is applicable only when the High Performance model QCPU is used.
* 6: For applicable GOT modules, refer to the following manuals.
• GOT-A900 Series User's Manual (GT Work2 Version2/GT Designer2
Version2 Compatible Connection System Manual)
• GOT1000 Series Connection Manual
Type
• QJ71GP21-SX
• QJ71GP21S-SX
• QJ71LP21
• QJ71BR11
• QJ71LP21-25
• QJ71LP21S-25
• QJ71LP21G
• QJ71LP21GE
• QJ71E71
• QJ71E71-B2
• QJ71E71-B5
• QJ71E71-100
• QJ61BT11
• QJ61BT11N
• A1SJ71PT32-S3
• A1SJ71T32-S3
• A1SD51S
• A1SD21-S1
• A1SJ71J92-S3
• A1SJ71AP23Q
• A1SJ71AR23Q
• A1SJ71AT23BQ
*5
• A1SI61
• QI60
GOT-A900 Series
*6
(for bus connection only)
GOT1000 Series
*6
(for bus connection only)
2.1 System Configuration
2.1.5 Precaution on system configuration
Limitation of installable modules
per system
Up to 2 modules
Up to 4 in total of
Total: Up to 4
PLC to PLC
modules
network and
remote I/O
network modules
Up to 4 modules
*4
No limit
No limit
(setting of automatic refresh function
not allowed)
Up to 6 modules in total
One unit only
One module only
Up to 5 modules
2
1
2
3
4
5
6
7
8
- 40

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents