12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
The memory copy from control system
6400
to standby system was executed, and
the program memory was cleared.
The memory copy from control system
to standby system was executed.
6410
(This can be detected from the control
system of the redundant system.)
The file register file specified in the
6500
tracking setting of the PLC parameter
dialog box does not exist.
The file register range specified in the
device detail setting of the tracking
6501
setting of the PLC parameter dialog box
exceeded the specified file register file
capacity.
*1
The module whose first 5 digits of serial No. is 09012 or later.
Corrective Action
After the memory copy from control
system to standby system is completed,
switch power OFF and then ON, or
make a reset.
Read the individual information of the
error using GX Developer, and check
and correct the drive name and file
name. Create the specified file.
Read the individual information of the
error using GX Developer, and increase
the file register capacity.
12.3 Error Code List
12.3.8 Error code list (6000 to 6999)
9
Corresponding
CPU
10
QnPRH
11
12
QnPRH
12
- 213