12
TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
4100
H
4101
H
4102
H
4103
H
4105
H
4106
H
Other errors
4107
H
4108
H
4109
H
410A
H
410B
H
4110
H
CPU mode
error
4111
H
12
- 228
12.3 Error Code List
12.3.11 Error codes returned to request source during communication with CPU module
Table12.12 Error code
Error details
CPU module hardware fault
Serial communication connection was
executed for a different CPU module series.
An attempt was made to erase the Flash ROM
during use of the file register.
The instruction written during RUN is wrong or
illegal.
CPU module internal memory hardware fault
The command cannot be executed since the
CPU module is performing system initialization
processing.
An attempt was made to perform the operation
of the function unavailable for the target CPU
module model name.
Operation cannot be made normally by device
monitor/test.
The specified operation cannot be executed
since the monitoring, set the condition for
other application in same computer, is in
execution.
The specified command cannot be executed
because of online prgram change.
The registration of monitoring condition was
canceled because of online program change.
Since the CPU module is in a stop error
status, it cannot execute the request.
The requested operation cannot be performed
since the other CPU modules have not yet
started in the multiple CPU system.
Corrective action
Change the CPU module.
Check the CPU module series.
Execute again after setting the CPU module to the STOP
status.
Execute online program change again, or write the
program after setting the CPU module to the STOP
status.
Change the CPU module.
Execute the operation again after the CPU module has
started.
Do not execute the function unsupported by the target
CPU module.
Execute device monitor/test again. Before execution,
check that access is not made to the access prohibited
area.
Execute the request again after deregistering the
monitoring condition on the same screen.
Execute the request again after the online program
change.
Execute the registration of monitoring condition again
after the online program change.
Execute the request again after resetting the CPU
module.
Execute the request again after the other CPU modules
have started.