Mitsubishi Q01CPU User Manual page 445

Melsec-q series, qcpu
Hide thumbs Also See for Q01CPU:
Table of Contents

Advertisement

12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
Automatic write to standard ROM was
performed on the CPU module that is
incompatible with automatic write to
standard ROM.
(Memory card where automatic write to
standard ROM was selected in the boot
file was fitted and the parameter enable
drive was set to the memory card.)
2400
The file designated at the PLC file
settings in the parameters cannot be
found.
The Ethernet parameter that was added
for QnACPU, with the function version
"B," has been set to QnACPU without
the function version "B."
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
*8
This applies to the QnUDE(H)CPU.
*9
The module whose first 5 digits of serial No. is 10042 or later.
Corrective Action
• Execute automatic write to standard
ROM on the CPU module which is
compatible with automatic write to
standard ROM.
• Using GX Developer, perform write of
parameters and programs to standard
ROM.
• Change the memory card for the one
where automatic write to standard
ROM has not been set, and perform
boot operation from the memory card.
• Read the individual information of the
error using peripheral device, check
to be sure that the parameter drive
name and file name correspond to
the numerical values there
(parameter number), and correct.
• Create a file created using
parameters, and load it to the CPU
module.
Change to QnACPU with the function
version "B".
Delete the Ethernet parameter.
12.3 Error Code List
12.3.4 Error code list (2000 to 2999)
9
Corresponding
CPU
10
*3
Qn(H)
QnPH
QnPRH
11
12
QnA
12
- 121

Hide quick links: