Electro Industries Shark 100S Installation & Operation Manual page 137

Electronic submeter with wifi ethernet capability
Hide thumbs Also See for Shark 100S:
Table of Contents

Advertisement

Modbus Address
Hex
Decimal
12-Bit Block
9C40 - 9C40 40001 - 40001 System Sanity Indicator
9C41 - 9C41 40002 - 40002 Volts A-N
9C42 - 9C42 40003 - 40003 Volts B-N
9C43 - 9C43 40004 - 40004 Volts C-N
9C44 - 9C44 40005 - 40005 Amps A
9C45 - 9C45 40006 - 40006 Amps B
9C46 - 9C46 40007 - 40007 Amps C
9C47 - 9C47 40008 - 40008 Watts, 3-Ph total
9C48 - 9C48 40009 - 40009 VARs, 3-Ph total
9C49 - 9C49 40010 - 40010 VAs, 3-Ph total
9C4A - 9C4A 40011 - 40011 Power Factor, 3-Ph total
9C4B - 9C4B 40012 - 40012 Frequency
9C4C - 9C4C 40013 - 40013 Volts A-B
9C4D - 9C4D 40014 - 40014 Volts B-C
9C4E - 9C4E 40015 - 40015 Volts C-A
9C4F - 9C4F 40016 - 40016 CT numerator
9C50 - 9C50 40017 - 40017 CT multiplier
9C51 - 9C51 40018 - 40018 CT denominator
9C52 - 9C52 40019 - 40019 PT numerator
9C53 - 9C53 40020 - 40020 PT multiplier
9C54 - 9C54 40021 - 40021 PT denominator
9C55 - 9C56 40022 - 40023 W-hours, Positive
9C57 - 9C58 40024 - 40025 W-hours, Negative
9C59 - 9C5A 40026 - 40027 VAR-hours, Positive
9C5B - 9C5C 40028 - 40029 VAR-hours, Negative
9C5D - 9C5E 40030 - 40031 VA-hours
9C5F - 9C5F 40032 - 40032 Neutral Current
9C60 - 9CA2 40033 - 40099 Reserved
9CA3 - 9CA3 40100 - 40100 Reset Energy Accumulators
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
Description
Format
12-Bit Readings Section
UINT16
0 or 1
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
2047 to 4095
UINT16
1047 to 3047
UINT16
0 to 2730
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
1 to 9999
UINT16
1, 10, 100
UINT16
1 or 5
UINT16
1 to 9999
UINT16
1, 10, 100
UINT16
1 to 9999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT16
0 to 4095
N/A
N/A
UINT16
password
End of Map
Doc# E145721
Units or
6
Range
Resolution
0 indicates proper meter operation
none
volts
2047= 0, 4095= +150
volts
volts = 150 * (register - 2047) / 2047
volts
amps
0= -10, 2047= 0, 4095= +10
amps
amps = 10 * (register - 2047) / 2047
amps
watts
0= -3000, 2047= 0, 4095= +3000
VARs
watts, VARs, VAs =
VAs
3000 * (register - 2047) / 2047
none
1047= -1, 2047= 0, 3047= +1
pf = (register - 2047) / 1000
Hz
0= 45 or less, 2047= 60, 2730= 65 or more
freq = 45 + ((register / 4095) * 30)
volts
2047= 0, 4095= +300
volts
volts = 300 * (register - 2047) / 2047
volts
none
none
CT = numerator * multiplier / denominator
none
none
PT = numerator * multiplier / denominator
none
none
Wh per energy format
* 5 to 8 digits
Wh per energy format
* decimal point implied, per energy format
VARh per energy format
* resolution of digit before decimal point =
VARh per energy format
units, kilo, or mega, per energy format
VAh per energy format
* see note 10
amps
see Amps A/B/C above
none
5
write-only register; always reads as 0
B: Modbus Map
#
Comments
Reg
read-only except as noted
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
1
67
1
Block Size:
100
MM-7