For Example: a reading for Digits: 8; Decimals: 3; Scale: k would be formatted:
00123.456k
Power Direction: View as Load or View as Generator
Demand Averaging
Averaging Method: Block or Rolling
Interval (Minutes): 5, 15, 30, or 60
Sub Interval (if Rolling is selected): 1-4
Auto Scroll
Click to set On or Off.
Display Configuration:
Click Values to be displayed.
NOTE: You MUST select at least ONE.
NOTE: If incorrect values are entered on this screen the following message appears:
WARNING: Current, CT, PT and Energy Settings will cause invalid energy accumulator
values.
Change the settings until the message disappears.
Electro Industries/GaugeTech
Electro Industries/GaugeTech