Electro Industries Shark 100S Installation & Operation Manual page 112

Electronic submeter with wifi ethernet capability
Hide thumbs Also See for Shark 100S:
Table of Contents

Advertisement

b. To change the value for the PT scaling:
From the Pt-S screen:
Use the Right button or the Down button to choose the scaling you want. The
Pt-S setting can be 1, 10, 100, or 1000.
NOTE: If you are prompted to enter a password, refer to Section 7.2.4 for instruc-
tions on doing so.
2. When the new setting is entered, press the Menu button twice.
3. The STOR ALL YES screen appears. Press Enter to save the new PT setting.
Example PT Settings:
277/277 Volts: Pt-n value is 277, Pt-d value is 277, Pt-S value is 1.
14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10.
138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100.
345,000/115 Volts: Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100.
345,000/69 Volts: Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000.
NOTE: Pt-n and Pt-S are dictated by primary voltage; Pt-d is secondary voltage.
MENU
ENTER
-
-
-
Use buttons to set Pt-n
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
MENU
ENTER
-
A
-
B
-
C
Use buttons to set Pt-d
7: Using the Submeter
-
A
-
B
-
C
Use buttons to select scaling
Doc
E145721
#
MENU
ENTER
A
B
C
7 - 12