Electro Industries Shark 100S Installation & Operation Manual page 152

Electronic submeter with wifi ethernet capability
Hide thumbs Also See for Shark 100S:
Table of Contents

Advertisement

These points are formatted as 2's complement fractions. They represent a fraction of
4500W Secondary in normal operation, or 3000W Secondary in Open Delta operation.
Inputs above/below +/-4500 or +/-3000W Secondary are pinned at +/-4500 or +/-
3000W Secondary, respectively.
Total VA (Point 12)
This point is formatted as a 2's complement fraction. It represents a fraction of
4500W Secondary in normal operation, or 3000W Secondary in Open Delta operation.
Inputs above/below +/-4500 or +/-3000W Secondary are pinned at +/-4500 or +/-
3000W Secondary, respectively.
Power Factor (Point 13)
This point is formatted as a 2's complement integer. It represents Power Factors from
-1.000 (0x0FC18) to +1.000 (0x003E8). In Open Delta operation, Total Power Factor
(Point 13) is always zero.
Frequency (Point 14)
This point is formatted as a 2's complement fraction. It represents the Frequency as
measured on Phase A Voltage in units of cHz (centiHertz, 1/100 Hz). Inputs below
45.00 Hz are pinned at 0 (0x0000); inputs above 75.00 Hz are pinned at 9999
(0x270F).
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Point
Reading
12
Total VA
Point
Reading
13
Power Factor Total
Point
Reading
14
Frequency
Doc
E145721
#
D: DNP 3.0 Protocol Assignments
D - 10