Modbus Address
Hex
Decimal
753E - 753E 30015 - 30015 User Settings Flags
753F - 753F 30016 - 30016 Full Scale Current (for load % bargraph)
7540 - 7547 30017 - 30024 Meter Designation
7548 - 7548 30025 - 30025 COM1 setup
7549 - 7549 30026 - 30026 COM2 setup
754A - 754A 30027 - 30027 COM2 address
754B - 754B 30028 - 30028 Limit #1 Identifier
754C - 754C 30029 - 30029 Limit #1 Out High Setpoint
754D - 754D 30030 - 30030 Limit #1 In High Threshold
754E - 754E 30031 - 30031 Limit #1 Out Low Setpoint
754F - 754F 30032 - 30032 Limit #1 In Low Threshold
7550 - 7554 30033 - 30037 Limit #2
7555 - 7559 30038 - 30042 Limit #3
755A - 755E 30043 - 30047 Limit #4
755F - 7563 30048 - 30052 Limit #5
7564 - 7568 30053 - 30057 Limit #6
7569 - 756D 30058 - 30062 Limit #7
756E - 7572 30063 - 30067 Limit #8
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
Description
Format
UINT16
bit-mapped
UINT16
0 to 9999
ASCII
16 char
UINT16
bit-mapped
UINT16
bit-mapped
UINT16
1 to 247
UINT16
0 to 65535
SINT16
-200.0 to +200.0
SINT16
-200.0 to +200.0
SINT16
-200.0 to +200.0
SINT16
-200.0 to +200.0
SINT16
SINT16
SINT16
same as Limit #1
SINT16
SINT16
SINT16
SINT16
Doc# E145721
Units or
6
Range
Resolution
---g--nn srp--wf-
g = enable alternate full scale bargraph
current (1=on, 0=off)
nn = number of phases for voltage &
current screens (3=ABC, 2=AB, 1=A,
0=ABC)
s = scroll (1=on, 0=off)
r = password for reset in use (1=on, 0=off)
p = password for configuration in use
(1=on, 0=off)
w = pwr dir (0-view as load, 1-view as
generator)
f = flip power factor sign (1=yes, 0=no)
none
If non-zero and user settings bit g is set,
this value replaces CT numerator in the full
scale current calculation.
none
----dddd -0100110
dddd = reply delay (* 50 msec)
ppp = protocol (1-Modbus RTU, 2-Modbus
ASCII, 3-DNP)
----dddd -ppp-bbb
bbb = baud rate (1-9600, 2-19200, 4-
38400, 6-57600)
none
use Modbus address as the identifier (see
notes 7, 11, 12)
0.1% of full scale
Setpoint for the "above" limit (LM1), see
notes 11-12.
0.1% of full scale
Threshold at which "above" limit clears;
normally less than or equal to the "above"
setpoint; see notes 11-12.
0.1% of full scale
Setpoint for the "below" limit (LM2), see
notes 11-12.
0.1% of full scale
Threshold at which "below" limit clears;
normally greater than or equal to the
"below" setpoint; see notes 11-12.
same as Limit #1
B: Modbus Map
#
Comments
Reg
1
1
8
1
1
1
1
1
1
1
1
5
5
5
same as Limit #1
5
5
5
5
Block Size:
68
MM-6