Electro Industries Shark 100S Installation & Operation Manual page 142

Electronic submeter with wifi ethernet capability
Hide thumbs Also See for Shark 100S:
Table of Contents

Advertisement

Object Point Var
Description
30
10
5 Watts, 3-Ph total
30
11
5 VARs, 3-Ph total
30
12
5 VAs, 3-Ph total
30
13
5 Power Factor, 3-Ph total
30
14
5 Frequency
30
15
5 Positive Watts, 3-Ph,
Maximum Avg Demand
30
16
5 Positive VARs, 3-Ph,
Maximum Avg Demand
30
17
5 Negative Watts, 3-Ph,
Maximum Avg Demand
30
18
5 Negative VARs, 3-Ph,
Maximum Avg Demand
30
19
5 VAs, 3-Ph, Maximum Avg
Demand
30
20
5 Angle, Phase A Current
30
21
5 Angle, Phase B Current
30
22
5 Angle, Phase C Current
30
23
5 Angle, Volts A-B
30
24
5 Angle, Volts B-C
30
25
5 Angle, Volts C-A
30
26
5 CT numerator
30
27
5 CT multiplier
30
28
5 CT denominator
30
29
5 PT numerator
30
30
5 PT multiplier
30
31
5 PT denominator
30
32
5 Neutral Current
Internal Indication
80
0
1 Device Restart Bit
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Format
Range
Multiplier
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
0 to +32767
(4500 / 32768)
SINT16
-1000 to +1000
0.001
SINT16
0 to 9999
0.01
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-32768 to +32767
(4500 / 32768)
SINT16
-1800 to +1800
0.1
SINT16
-1800 to +1800
0.1
SINT16
-1800 to +1800
0.1
SINT16
-1800 to +1800
0.1
SINT16
-1800 to +1800
0.1
SINT16
-1800 to +1800
0.1
SINT16
1 to 9999
N/A
SINT16
1, 10, or 100
N/A
SINT16
1 or 5
N/A
SINT16
1 to 9999
N/A
SINT16
1, 10, or 100
N/A
SINT16
1 to 9999
N/A
SINT16
0 to 32767
(10 / 32768)
N/A
N/A
N/A
Doc# E145721
Units
Comments
W
VAR
VA
none
Hz
W
VAR
W
VAR
VA
degree
degree
degree
degree
degree
degree
none
CT ratio =
none
(numerator * multiplier) / denominator
none
none
PT ratio =
none
(numerator * multiplier) / denominator
none
A
For 1A model, multiplier is (2 / 32768) and
values above 2A secondary read 32767.
none
Clear via Function 2 (Write), Qualifier Code
0.
C: DNP Map
DNP-2

Advertisement

Table of Contents
loading

Table of Contents