Modbus Address
Hex
Decimal
Identification Block
0000 - 0007
1 - 8
Meter Name
0008 - 000F
9 - 16
Meter Serial Number
0010 - 0010
17 - 17
Meter Type
0011 - 0012
18 - 19
Firmware Version
0013 - 0013
20 - 20
Map Version
0014 - 0014
21 - 21
Meter Configuration
0015 - 0015
22 - 22
ASIC Version
0016 - 0026
23 - 39
Reserved
0027 - 002E
40 - 47
Reserved
Primary Readings Block, 6 cycles (IEEE Floating Point)
0383 - 0384
900 - 901
Watts, 3-Ph total
0385 - 0386
902 - 903
VARs, 3-Ph total
0387 - 0388
904 - 905
VAs, 3-Ph total
Primary Readings Block, 60 cycles (IEEE Floating Point)
03E7 - 03E8
1000 - 1001
Volts A-N
03E9 - 03EA
1002 - 1003
Volts B-N
03EB - 03EC
1004 - 1005
Volts C-N
03ED - 03EE
1006 - 1007
Volts A-B
03EF - 03F0
1008 - 1009
Volts B-C
03F1 - 03F2
1010 - 1011
Volts C-A
03F3 - 03F4
1012 - 1013
Amps A
03F5 - 03F6
1014 - 1015
Amps B
03F7 - 03F8
1016 - 1017
Amps C
03F9 - 03FA
1018 - 1019
Watts, 3-Ph total
03FB - 03FC
1020 - 1021
VARs, 3-Ph total
03FD - 03FE
1022 - 1023
VAs, 3-Ph total
03FF - 0400
1024 - 1025
Power Factor, 3-Ph total
0401 - 0402
1026 - 1027
Frequency
0403 - 0404
1028 - 1029
Neutral Current
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
Description
Format
Fixed Data Section
ASCII
16 char
ASCII
16 char
UINT16
bit-mapped
ASCII
4 char
UINT16
0 to 65535
UINT16
bit-mapped
UINT16
0-65535
Meter Data Section
FLOAT
-9999 M to +9999 M
FLOAT
-9999 M to +9999 M
FLOAT
-9999 M to +9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
0 to 9999 M
FLOAT
-9999 M to +9999 M
FLOAT
-9999 M to +9999 M
FLOAT
-9999 M to +9999 M
FLOAT
-1.00 to +1.00
FLOAT
0 to 65.00
FLOAT
0 to 9999 M
Doc# E145721
Units or
6
Range
Resolution
none
none
-------t -----vvv
t = transducer model (1=yes, 0=no),
vvv = V-switch(1 to 4)
none
none
-------- --ffffff
ffffff = calibration frequency (50 or 60)
none
2
watts
VARs
VAs
volts
volts
volts
volts
volts
volts
amps
amps
amps
watts
VARs
VAs
none
Hz
amps
B: Modbus Map
#
Comments
Reg
read-only
8
8
1
2
1
1
1
17
8
Block Size:
47
read-only
2
2
2
Block Size:
6
read-only
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Block Size:
30
MM-1