Apparent Energy Total [VAh] 0.2% of reading
Power Factor
Frequency
Total Harmonic Distortion
(%)
Load Bar
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of
reading.
• For 1A (Class 2) Nominal, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, the input current range for Accuracy specification is
20% of the values listed in the table.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale
threshold (for example, 120V/120V/208V system), degrade accuracy by additional
0.4%.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
1,2
1,2
0.2% of reading
+/- 0.01Hz
1,
5.0%
+/- 1 segment
Doc
#
2: Meter Overview and Specifications
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
(45 to 65)Hz
(0.5 to 10)A or (69 to
480)V, measurement range
(1 to 99.99)%
(0.005 to 6)A
E145721