D.4.1.5: Class 0 Data (Obj. 60, Var. 1)
Class 0 Data supports the following functions:
Read (Function 1)
A request for Class 0 Data from a Shark® 100S meter returns three Object Headers.
Specifically, it returns 16-Bit Analog Input Without Flags (Object 30, Variation 4),
Points 0 - 31, followed by 32-Bit Counters Without Flags (Object 20, Variation 5),
Points 0 - 4, followed by Binary Output Status (Object 10, Variation 2), Points 0 - 1.
(There is NO Object 1.)
A request for Object 60, Variation 0 is treated as a request for Class 0 Data.
D.4.1.6: Internal Indications (Obj. 80, Var. 1)
Internal Indications support the following functions:
Write (Function 2)
Internal Indications may be indexed by Qualifier Code 0.
Device Restart (Point 0)
This bit is set whenever the meter resets. The polling device may clear this bit by
Writing (Function 2) to Object 80, Point 0.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
D: DNP 3.0 Protocol Assignments
Doc
E145721
#
D - 13