Setpoint delta increase (HEAT) or decrease (COOL) – in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode,
while in EconoMode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in EconoMode.
4.3.3 Enable use of ADDITIONAL HEATING mode
This parameter shows/hides the Control_ Start Additional Heat Mode and Status_ Additional
Heat Mode communication objects. The Additional Heating Mode lets change the Setpoint
Temperature and the Fan Speed within a given period of time.
If set to "no" the objects will not be shown.
o
If set to "yes" the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode
o
objects and new parameters will appear.
When a "1" value is sent to the Control_ communication object, Additional
Heating Mode will be enabled, and the Status_ object will return this value.
When a "0" value is sent to the Control_ communication object, Additional
Heating Mode will be disabled, and the Status_ object will return this value.
Important: This mode will ALWAYS turn on the indoor unit in Heat mode.
Action time for this mode (minutes):
Duration of Additional Heating Mode, in minutes, once started.
Setpoint temp for this mode (ºC):
Setpoint temperature that will be applied while in Additional Heating Mode.
Fan Speed for this mode:
Fan Speed that will be set in the unit while in Additional Heating Mode.
4.3.4 Enable use of ADDITIONAL COOLING mode
This parameter shows/hides the Control_ Start Additional Cool Mode and Status_ Additional
Cool Mode communication objects. The Additional Heating Mode lets change the Setpoint
Temperature and the Fan Speed within a given period of time.
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
User's manual r1.0 eng
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
21 / 66
Need help?
Do you have a question about the DK-RC-KNX-1i and is the answer not in the manual?
Questions and answers