IntesisBox
KNX - Daikin A.C. (SKY & VRV line)
60
Status_ Mode Text
Status_ Fan Speed / 2 Speeds
Status_ Fan Speed / 3 Speeds
61
Status_ Fan Speed / 2 Speeds
Status_ Fan Speed / 3 Speeds
Fan Speed
62
Status_ Fan Speed 1
63
Status_ Fan Speed 2
64
Status_ Fan Speed 3
65
Status_ Fan Speed Text
Status_ Vane Up-Down / 5 pos
66
Status_ Vane Up-Down / 5 pos
67
Status_ Vane Up-Down Swing
68
Status_ Vane Up-Down Pos1
Vanes
69
Status_ Vane Up-Down Pos2
70
Status_ Vane Up-Down Pos3
71
Status_ Vane Up-Down Pos4
72
Status_ Vane Up-Down Pos5
73
Status_ Vane Up-Down Text
Temperature
74
Status_ AC Setpoint Temp
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
14 byte
DPT_String_8859_1
16.001
1 byte
DPT_Scaling
5.001
1 byte
DPT_Scaling
5.001
1 byte
DPT_Scaling
5.001
1 byte
DPT_Scaling
5.001
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
14 byte
DPT_String_8859_1
16.001
1 byte
DPT_Scaling
5.001
1 byte
DPT_Enumerated
5.010
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
14 byte
DPT_String_8859_1
16.001
2 byte
DPT_Value_Temp
9.001
R
T
ASCII String
R
T
50% - Speed 1; 100% - Speed 2
33% - Speed 1; 67% - Speed 2; 100% -
R
T
Speed 3
R
T
1 - Speed 1; 2 - Speed 2
R
T
1 - Speed 1; 2 - Speed 2; 3 - Speed 3
R
T
1 - Speed 1
R
T
1 - Speed 2
R
T
1 - Speed 3
R
T
ASCII String
20% - Pos1; 40% - Pos2; 60% - Pos3;
R
T
80% - Pos4; 100% - Pos5
1 - Pos1; 2 - Pos2; 3 - Pos3;
R
T
4 - Pos4; 5 - Pos5
R
T
0 - Stop; 1 - Swing
R
T
1 - Position 1
R
T
1 - Position 2
R
T
1 - Position 3
R
T
1 - Position 4
R
T
1 - Position 5
R
T
ASCII String
R
T
16ºC to 32ºC
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
User's manual r1.0 eng
64 / 66
Need help?
Do you have a question about the DK-RC-KNX-1i and is the answer not in the manual?