If set to "no" the remote controller will work as usually. It also appears a new parameter
o
and the communication object Control_ Lock Remote Control.
Enable comm obj "Ctrl_ Remote Lock":
If set to "no" the object will not be shown.
If set to "yes" the Control_ Lock Remote Control object will appear.
When a "1" value is sent to this communication object, the remote controller
is locked. To be unlocked a "0" value must be sent. The gateway remembers
the last value received even if a KNX bus reset/failure happens.
Important: If an initial scene is enabled and it has as Value for Remote Lock
(unchanged) or unlocked, this would unlock the remote controller because the
initial scene has priority over the Control_ Lock Remote Control communication
object.
4.1.5 Enable func "Control_ Lock Control Obj"
This parameter shows/hide the Control_ Lock Control Obj communication object which,
depending on the sent value, locks or unlocks ALL the Control_ communication objects except
itself.
If set to "no" the object will not be shown.
o
If set to "yes" the Control_ Lock Control Objects object will appear.
o
When a "1" value is sent to this communication object, all the Control_ objects
will be locked. To unlock a "0" value must be sent, as the gateway remembers
the last value received even if a KNX bus reset/failure happens.
4.1.6 Enable func "Operating Hours Counter"
This parameter shows/hides the Status_ Operation Hour Counter communication object which
counts the number of operating hours for the DK-RC-KNX-1i.
If set to "no" the object will not be shown.
o
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SL
Figure 4.6 Communication object and parameter detail
User's manual r1.0 eng
URL
http://www.intesis.com
Email
info@intesis.com
tel
+34 938047134
13 / 66
Need help?
Do you have a question about the DK-RC-KNX-1i and is the answer not in the manual?
Questions and answers