KNX - Daikin A.C. (SKY & VRV line)
4.7.3 Enable use of bit objects for scene execution
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.
If set to "no" the communication objects will not be shown.
o
If set to "yes" the communication objects will appear. To execute a scene by using these
o
objects, a "1" value has to be sent to the scene's object we want to execute (i.e. to
execute scene 4, a "1" has to be sent to the Control_ Execute Scene 4 object).
4.7.4 Scene "x" preset
This parameter lets you define a preset for a scene (the following description is valid for all
the scenes).
If set to "no" the preset for the scene "x" will be disabled.
o
If set to "yes" the preset will be enabled. When a scene is executed the values configured
o
in the preset will be aplied.
Important: If a scene's preset is enabled, will not be possible to modify (store) the scene
from the KNX bus.
© Intesis Software S.L. - All rights reserved