Electrical Requirements

Note -
distance of the server from the doors, can affect the cooling performance of the server.
You must evaluate these restrictions. Server placement is particularly important for high-
temperature environments.
Manage cables to minimize interference with the server exhaust vent.

Electrical Requirements

The servers use AC power. The following table contains the power supply specifications for the
servers.
The power dissipation numbers listed in the following table are the maximum rated
Note -
power numbers for the power supply used in the server. The numbers are not a rating of the
actual power consumption of the server. For up-to-date information about power consumption,
go to the Oracle Power Calculators web site:
storage/sun-power-calculators/index.html, and click the Oracle Server X7-2 or Oracle
Server X7-2L link.
Parameter
Voltage (nominal)
Input current (maximum)
Frequency (nominal)
Maximum power consumption
Maximum heat output
The servers can operate effectively over a range of voltages and frequencies.
18
Oracle Servers X7-2 and X7-2L Installation Guide • October 2017
The combination of inlet and exhaust restrictions, such as cabinet doors and the
http://www.oracle.com/us/products/servers-
Specification
100-240 VAC
100-127 VAC 7.2 A and 200-240 VAC 3.4 A
50/60 Hz (47 to 63 Hz range)
2400 W
11600 BTU/Hr