Environmental Requirements
This topic includes these specifications:
Temperature, humidity, and elevation
■
Shock and vibration
■
Acoustic
■
TABLE 1
Temperature, Humidity, and Elevation Specifications
Operating
Description
Metric
Temperature
5° to 35° C
(maximum)
at 900m
Relative
10 to 80%
humidity
at 27° C
Altitude
0 to 3000 m
at 40° C
TABLE 2
Description
Shock
Vibration (vertical)
Vibration (horizontal)
TABLE 3
Description
Sound Power Level - LwAd
Nonoperating
U.S.
Metric
41° to 95° F at 0
-40° to 65° C
to 3000 ft
at 900m
10 to 80%
Up to 85%
at 81° F
at 38° C
0 to 9840 ft at
Up to 12,000 m
95° F
Shock and Vibration Specifications
Operating
3 G, 11 ms
0.15 G
0.10 G
Acoustic Specifications
U.S.
-40° to 149° F
at 0 to 3000 ft
Up to 85%
at 100° F
Up to 40,000 ft
Notes
Half-sine
5 to 500 HZ swept-sine
Operating at 60%
8.7 B
Environmental Requirements
Notes
Decrease in maximum
temperature: above 3000 ft.
(900m), 1.8°F/1000 ft (1°
C/300m)
Maximum wet bulb,
noncondensing
In China markets, regulations
may limit installations to a
maximum operating altitude of
2000m.
Operating at 100%
9.9 B
Confirming Specifications
19