Environmental Requirements
Specification
Altitude
Acoustic noise
Vibration
Shock
Related Information
"Temperature Guidelines" on page 16
■
"Humidity Guidelines" on page 16
■
"Ventilation and Cooling Requirements" on page 17
■
Temperature Guidelines
An ambient temperature range of 21° to 23° Celsius (70° to 74° Fahrenheit) is optimal for
server reliability and operator comfort. Most computer equipment can operate in a wide
temperature range, but approximately 22° Celsius (72° Fahrenheit) is recommended because it
is easier to maintain safe humidity levels. Operating in this temperature range provides a safety
buffer in the event that the air conditioning system is not running for a period of time.
Humidity Guidelines
The ambient relative humidity range of 45 to 50 percent is acceptable for safe data processing
operations. Most computer equipment can operate in a wide range (20 to 80 percent), but 45 to
50 percent is the recommended optimal range for the following reasons:
Helps protect computer systems from corrosion problems associated with high humidity
■
levels.
16
Oracle Servers X7-2 and X7-2L Installation Guide • October 2017
Operating
Up to 9,840 feet (3,000 meters)
Note -
In China markets, regulations may
limit installations to a maximum altitude of
6,562 feet (2,000 meters).
■ Maximum condition: 7.1 Bels A
weighted
■ Idle condition: 7.0 Bels A weighted
■ 0.15 G (z-axis)
■ 0.10 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
3.5 G, 11 ms half-sine
IEC 60068-2-27 Test Ea
Nonoperating
Maximum 39,370 feet (12,000 meters)
Not applicable
■ 0.5 G (z-axis),
■ 0.25 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
■ Roll-off: 1.25-inch roll-off free fall, front
to back rolling directions
■ Threshold: 13-mm threshold height at
0.65 m/s impact velocity
■ ETE-1010-02 Rev A
Need help?