Electrical Power Requirements - Oracle X5-2 Installation Manual

Hide thumbs Also See for X5-2:
Table of Contents

Advertisement

Electrical Power Requirements

Location
Front of the server

Electrical Power Requirements

The Oracle Server X5-2 uses AC power. The following table lists the power supply
specifications for the server.
Note -
power numbers for the power supply used in the system. The numbers are not a rating of
the actual power consumption of the system. For up-to-date information about the power
consumption, go to Oracle Power Calculators web site and click on the Oracle Server X5-2 link:
https://www.oracle.com/it-infrastructure/power-calculators/
TABLE 5
Parameter
Voltage (nominal)
Input current (maximum)
Frequency (nominal)
The Oracle Server X5-2 can operate effectively over a range of voltages and frequencies.
However, it must have a reliable power source. Damage to the server might occur if the ranges
are exceeded. Electrical disturbances such as the following might damage the system:
Fluctuations caused by brownouts
Wide and rapid variations in input voltage levels or in input power frequency
Electrical storms
Faults in the distribution system, such as defective wiring
To protect your server from such disturbances, you should have a dedicated power distribution
system, power-conditioning equipment, as well as lightning arresters or power cables to protect
from electrical storms.
See the following sections for additional power specifications.
"Facility Power Guidelines" on page 19
"Circuit Breaker and UPS Guidelines" on page 19
18
Oracle Server X5-2 Installation Guide • January 2021
Maintenance Access Requirement
123.2 cm (48.5 inches)
The power dissipation numbers listed in the following table are the maximum rated
Power Supply Specifications
Specification
100 to 127 VAC; 200 to 240 VAC
7.2 A @ 100-127 VAC; 3.4 A @ 200-240 VAC
50/60 Hz (47 to 63 Hz range)