Downloading Code Files
Download Procedure, continued
Note
If the iBox does not have a code file loaded, or if it has detected a corrupt flash file,
you will have to go directly to Step 8 and log directly into the monitor.
Step
3
4
5
6
7
!
While the iBox is rebooting, the system is disabled.
8
9
10
GE Information
, continued
Launch System Monitor
Log into WESMAINT.
Select option 2, System Functions.
Select option 3, 68K Monitor.
Result: The D25A> prompt appears, indicating that the Application
Monitor is running.
At the D25A> prompt type rtb
For other available commands type help
At the Return to the BootROM Operating System? (yes/no) prompt,
type yes and press
ENTER
Note: The monitor is not case-sensitive, but Y is not acceptable
Result: The system restarts.
Log in to the System Monitor
After the restart is complete, press
Result: The Login: prompt appears.
Type the login name westronic
Result: The system performs self-diagnostics to ascertain whether any
Flash EPROM memory is in use. The D25S> prompt appears,
indicating the System Monitor is running.
Clear Flash EPROM
Type erase and press
ENTER
Result: The recommended procedure is to clear flash EPROM
memory, no matter what the system check reveals.
Installation and Maintenance Guide
Action
.
ENTER
.
ENTER
.
ENTER
and password rd
ENTER
(not case-sensitive).
994-0047-5.10-4
iBox/iBox Kit
.
ENTER
Continued on next page
67