GE iBox Installation And Maintenance Manual page 144

Grid solutions
Table of Contents

Advertisement

iBox/iBox Kit
Installation and Maintenance Guide
Technical Specifications – iBox
Digital
General
Outputs
Security features
Control Voltage
Switching Characteristics
Maximum Carrying Current
Size and
Dimensions
Environment
Weight
Operating Temperature
Storage Temperature
Humidity Rating
Operating Altitude
Environmental Rating
Installation (Overvoltage)
Category
Pollution Degree
IEC 68-2-1
IEC 68-2-2
IEC 68-2-6
IEC 68-2-30
MTBF
144
, continued
Up to four relay outputs: 4 Trip/Close pairs or 2
Trip/Close pairs and 2 Form A contacts
Separate Master Trip and Master Close relays
Single point of failure integrity, select-before-
operate (SBO) functionality. Remote/Local jumper
JP2.
External
35 W breaking @ 150 Vdc
180 W breaking @ 30 Vdc
6 A
Width (of Mounting
Panel)
Height
Depth
1 kg (2.2 lb) maximum
-40° to +80°C, may exceed EN61010-1 metal
enclosure temperature of +70° C at ambient
temperature of +60°C.
-40° to +90°C
0 to 95% relative humidity, non-condensing
0 to 2000 meters
IP20
CAT II EN61010-1
Note: Must be installed in an overall protective
enclosure and/or a protective environment unless
the power supply terminals have a protective cover
installed
2
Cold
Dry heat
Vibration
Damp heat, cyclic (12+12-hour cycle)
> 74000 hours @ 40°C
Note: Increased operating temperature decreases
MTBF of the device
994-0047-5.10-4
GE Grid Solutions
28 cm (11 inch)
19 cm (7.5 inch)
4.5 cm (1.75 inch)
Continued on next page