Control
The iBox provides the following control outputs:
Outputs
Four Trip/Close pairs, or two Trip/Close pairs and two Form A contacts.
Separate Master Trip and Master Close relays
Security features:
35 W breaking @ 125 VDC, 180 W breaking @ 30 VDC
6 A current handling capability
26
Protection against erroneous operation due to single point of failure
Select-before-operate (SBO) functionality